Conventional vs IO-Link Signal Lights: Technical Comparison and Selection Criteria

Conventional vs IO-Link Signal Lights: Technical Comparison and Selection Criteria

Geschreven doorUSP

A technical comparison of control architecture, wiring, commissioning, diagnostics, response time and lifecycle cost for industrial machine signaling.

A conventional signal light is often the most direct choice when a machine requires a limited number of fixed states. An IO-Link signal light becomes more relevant when signaling behaviour must be parameterised, reused across machine variants, monitored or changed without modifying the physical wiring. Neither architecture is inherently preferable. Selection depends on the required signals, the existing control architecture and the operational value of additional device data throughout the machine lifecycle.

This distinction matters because a status light forms part of the interface between a machine and the people working around it. If the indication is unclear, operators may take longer to identify a material shortage, process interruption or maintenance request. At the same time, communication hardware and software should only be added when their functions provide a defined engineering or operational benefit.

The following comparison evaluates both architectures in terms of I/O allocation, wiring, commissioning, parameter management, diagnostics, response time and lifecycle cost. It also identifies the conditions under which conventional control remains the more proportionate engineering decision.

Selection principle: use conventional control for a small number of stable signaling states and a direct electrical architecture. Use IO-Link when central parameterisation, reusable configurations, device data or parameter recovery creates measurable value during engineering, operation or maintenance.

Conventional signal-light control architecture

A conventionally controlled signal light receives discrete electrical signals from a PLC output, relay or another control component. Depending on the design, separate inputs may activate individual colours, tower stages, audible functions or predefined signaling patterns.

The exact method varies by product. A single-colour beacon may only require an on or off signal. A multi-colour RGB indicator may accept several control inputs that represent different colours or functions. A modular signal tower may have separate connections for its individual stages. The controller determines which outputs are active, while the signaling device converts those electrical states into visible or audible indications.

This architecture is transparent and supports direct electrical troubleshooting. A technician can trace the signal from the PLC output to the device using the electrical drawing and standard measurement equipment. If a machine requires only a few stable indications, conventional control can provide the required functionality without adding a communication layer.

IO-Link signal-light control architecture

IO-Link is a globally standardised I/O technology specified in IEC 61131-9. It provides serial, bidirectional, point-to-point communication between one IO-Link master port and one field device. The master connects the field-level device to the PLC and the higher-level industrial network.

With an IO-Link signal light, the connection is used not only to issue signaling commands but also to exchange device information. Depending on the functions supported by the specific device, the automation system can select colours and signaling modes, adjust parameters, read identification data and receive diagnostic or event information.

Process data is exchanged cyclically for normal device operation. Parameters, identification information, diagnostic data and events are transferred acyclically. The supported data and functions are defined in the device documentation and its IO Device Description, or IODD. The related Machine Safety Shop guide to IO-Link explains the communication structure in more detail.

Selection factor Conventional signal light IO-Link signal light
Control architecture Discrete PLC outputs or relay signals Point-to-point communication through an IO-Link master
Configuration Defined by wiring, device settings and PLC logic Device parameters can be configured through the IO-Link system when supported
Device feedback and data No device data is returned unless separate feedback or monitoring is provided Process data, parameters, identification data and events may be available
Wiring May use multiple control conductors or outputs for several functions One point-to-point communication connection per device. Conductor count depends on the port class and power requirements
Additional hardware PLC outputs, relays or interface modules as required IO-Link master port and compatible engineering environment required
Device replacement Replacement device may require manual settings and verification Stored parameters may be transferred automatically when supported and configured
Diagnostics Mainly based on PLC output state, wiring checks and visual inspection Device and communication diagnostics may be available to the controller
Typical application Fixed and limited signaling requirements Variable or configurable signaling with a defined requirement for device data

The table provides a general comparison. The available functions depend on the selected signal light, IO-Link master and PLC implementation. IO-Link capability does not imply that every diagnostic or parameter function is supported.

Control of colours and signaling modes

With conventional control, the available states are determined by the device inputs and the PLC logic. If three outputs correspond to three colours, the engineer must define which output combinations are valid and how they are used. Flashing may be generated by the device, by PLC logic or by an external module, depending on the product.

This is adequate for a machine with a stable signaling concept. For example, a machine may use green for normal operation, amber for an operator request and red for a fault. If these states and their behaviour remain fixed, IO-Link adds limited value solely for controlling the indication.

An IO-Link signal light provides more configuration options when supported colours, brightness levels, flashing frequencies or signaling modes must be parameterised. The same physical device can then be used across different machine variants while its behaviour is defined by a controlled parameter set.

The additional flexibility still requires a consistent signaling specification. More available colours and patterns do not automatically improve communication. Identical states should retain the same meaning throughout the machine or production area.

Wiring, I/O allocation and master requirements

A conventional multi-function signal light may require several controller outputs, depending on the number of functions and the electrical design of the product. This affects the PLC output count, terminal arrangement, cable cores and electrical documentation.

IO-Link transmits control data and device information through a point-to-point connection between the master port and the signal light. The official IO-Link system description specifies standard unshielded three-conductor or five-conductor cables, depending on the port class and power requirements.

IO-Link does not remove the need for field wiring or control hardware. Every device requires a physical connection to a master port, and the master must be powered and integrated into the control system. If no IO-Link infrastructure is present, adding a master solely for one fixed-function signal light may require more hardware and engineering than conventional control.

The comparison should therefore be made at system level. Count the required PLC outputs, terminal points, cables, master ports, cabinet space and engineering time. For an IO-Link actuator such as a signal light, also verify the port class, available output current and total power budget of the master. A solution with fewer conductors at the device is not necessarily the least expensive architecture overall.

Commissioning and machine variants

Conventional signal lights are normally commissioned by checking the wiring and testing each commanded state. Device-specific settings may need to be adjusted locally. A fixed configuration with few functions generally requires limited commissioning effort.

IO-Link allows supported device settings to be managed in the engineering environment. Parameters can be assigned centrally through the master using the device IODD. This is relevant when an OEM builds multiple machine variants with different signaling requirements. A standard hardware design can be retained while signaling behaviour is adapted through controlled parameter sets.

This does not eliminate commissioning work. The master must be integrated into the automation network, its ports must be configured, the IODD must be managed and the process data must be mapped correctly in the PLC. Naming conventions and version management also become important when settings are reused across machines.

The advantage of IO-Link increases when the integration work can be standardised and reused. For a one-off machine with only a few fixed signals, conventional control may require less engineering effort.

Diagnostics and maintenance data

A PLC can confirm that it has switched a conventional output, but this does not necessarily prove that the signal light is functioning or that its connection is intact. Troubleshooting may require inspection of the output, wiring, connector and device.

IO-Link enables bidirectional communication. The IO-Link Community defines cyclic process data as well as acyclic device data and events. Depending on the signal light, this can make operating status, device identification, communication faults or maintenance information available to the controller or HMI.

The practical value depends on the functions implemented by the manufacturer. IO-Link compatibility alone does not confirm lamp-health monitoring, internal fault detection or predictive maintenance data. Before selecting a device for diagnostic purposes, engineers should review its IODD, data sheet and operating instructions to determine which data is actually available.

Where supported data is integrated into the PLC and maintenance process, IO-Link can reduce troubleshooting time. If the information is collected but never displayed, logged or acted upon, the technical capability provides little operational benefit.

Device replacement and parameter recovery

Replacing a conventional signal light generally involves installing an electrically compatible product, checking any local settings and testing every required state. This is straightforward when the replacement is identical and has few configurable functions.

IO-Link can support parameter storage and automatic parameter reassignment when both the master and device support the required functions and the system is configured accordingly. The stored settings can then be transferred to a compatible replacement device. This can reduce the risk of incorrect manual settings and shorten replacement time.

Automatic parameter transfer is conditional on device compatibility, IO-Link version, master configuration and the selected data-storage settings. These points must be verified during engineering. Maintenance documentation should still identify the approved replacement device and define the functional test required after installation.

Update time and control-system response

A conventional output changes according to the PLC program, output-module update and electrical response of the device. With IO-Link, the signaling command is included in the cyclic process-data exchange. The resulting update time depends on the device’s minimum cycle time, master processing, PLC task and higher-level network architecture.

For normal status indication, this difference is rarely decisive. It must still be assessed where an indication has a specified maximum update time or where several communication layers are involved. The IODD and master documentation provide the values required for the response-time calculation. Neither conventional status signaling nor standard IO-Link communication should be assumed to implement a safety-related response.

Capital cost and total lifecycle cost

The unit price of a conventional signal light may be lower, and the device can often use existing PLC outputs. For a small installation, this can make conventional control the lower-cost architecture.

An IO-Link solution may involve a higher device price, allocation of a master port and additional configuration and integration time. These costs arise during the project. Potential lifecycle savings may result from standardised wiring, central configuration, reuse of parameter sets, access to diagnostic information and faster replacement.

The correct financial comparison is therefore not limited to the price of the signal light. It should include:

-PLC outputs and interface hardware

-IO-Link master capacity

-cabling and installation labour

-software engineering and commissioning

-documentation for machine variants

-troubleshooting time

-replacement time and risk of incorrect settings

-spare-parts strategy

For a single fixed-function light, additional IO-Link infrastructure may not be justified. Across a machine platform with multiple configurable devices, lifecycle savings can offset the higher initial cost when the supported functions are integrated and used.

Selection matrix by application requirement

Application requirement Preferred starting point
A small number of fixed states Conventional control
Existing spare PLC outputs and no available IO-Link port Conventional control
Direct electrical troubleshooting is preferred Conventional control
Colours or signaling modes vary between machine versions IO-Link
Central parameterisation and reusable configurations are required IO-Link
Device identification, events or supported diagnostic data must be available in the PLC or HMI IO-Link
Parameter recovery should support device replacement IO-Link
An existing IO-Link architecture has suitable spare port and power capacity IO-Link

This table is a starting point, not an automatic selection rule. Conventional control is proportionate when the required function is fixed and limited. The case for IO-Link becomes stronger when several data, configuration and maintenance functions will be implemented and used.

Hybrid control architectures within one machine

A machine does not need to use one control method for every signaling device. A hybrid architecture can be appropriate when the functional requirements differ by signaling point.

A fixed-function beacon may remain conventionally controlled, while a configurable RGB status indicator on the main operator station uses IO-Link. Existing machine modules can retain established wiring, while new modules adopt IO-Link where its configuration and diagnostic functions provide value.

The design should remain consistent from the operator’s perspective. A red fault indication, amber request or blue operator call should not change meaning merely because one device uses conventional control and another communicates through IO-Link.

Pfannenberg devices for both control architectures

Pfannenberg provides both conventional and IO-Link versions of selected RGB signaling devices. The INTENSE BAR S, INTENSE BAR M and INTENSE DOME 50 are available as conventional M12-connected variants and as IO-Link variants. This allows the form factor to be selected according to visibility and mounting requirements, while the control method is selected separately.

For applications requiring combined visual and audible indication, an IO-Link version of the PA L 1-R RGB is available. The modular BR 50 signal tower can also be integrated through dedicated IO-Link modules. The related Machine Safety Shop article on Pfannenberg machine status indicators compares the available product formats and their installation characteristics.

Before ordering, confirm the product number, supply voltage, current consumption, M12 pin assignment, IP rating, available IO-Link master port, port class, power budget and IODD version. Specifications from a conventional version must not be applied to the corresponding IO-Link version without verification.

Engineering checklist before product selection

Use the following questions during the electrical and automation design review:

-How many machine states must the device communicate?
-Will the colours or signaling modes change between machine variants?
-How many PLC outputs would conventional control require?
-Is an IO-Link master already available, and does it have a suitable free port, port class and power capacity?
-Which parameters, process data and events are actually supported by the device?
-Will the diagnostic information be integrated into the HMI or maintenance process?
-Is automatic parameter recovery required after device replacement?
-What are the commissioning, software-version and documentation requirements?
-Which option has the lowest total cost over the expected machine lifecycle?
-Has the signaling concept been assessed separately from the machine safety functions?

The selection should be based on these application requirements rather than on a general preference for conventional wiring or digital communication.

Select the control architecture against the application requirements

Conventional signal lights remain appropriate for fixed, clearly defined machine states. They provide a direct architecture and can be cost-effective when no additional device data or parameterisation is required.

IO-Link signal lights are appropriate when configuration, diagnostics, device identification, parameter recovery or reuse across machine variants has a defined requirement. Their technical value depends on whether the available communication and data functions are implemented in the engineering, operating and maintenance processes.

The selected solution must communicate the required machine states clearly while matching the control architecture, integration effort, maintenance strategy and lifecycle-cost requirements.

Technical support for control architecture and product selection

Machine Safety Shop can help assess the required signaling states, mounting position, electrical connection, IO-Link architecture and environmental conditions for the application.

Primary CTA: View conventional and IO-Link signal lights
Secondary CTA: Request technical advice

Frequently asked questions

How does IO-Link affect signal update time?

IO-Link and conventional output architectures have different timing characteristics. IO-Link update time depends on the device cycle time, master processing and PLC configuration. Applications with a defined maximum response time require a calculation based on the selected components.

Which master-port parameters must be verified?

Verify the port class, available output current, total master power budget, connector pin assignment, supported IO-Link version and process-data capacity. A free port is suitable only when its electrical and communication characteristics meet the device requirements.

Which diagnostic data is available from an IO-Link signal light?

IO-Link supports device data and events, but the available information depends on the functions implemented by the manufacturer. The IODD and technical documentation define which status, identification, warning and fault data is available.

Can standard IO-Link be used for a safety-related signaling function?

Standard IO-Link communication and RGB signaling do not by themselves provide a required Performance Level or SIL. Safety-related functions must be determined through the machine risk assessment and implemented with suitable components and architecture.

When can IO-Link reduce wiring costs?

IO-Link can reduce the number of discrete control signals required for a multi-function device, but it also requires a master port and engineering integration. Any cost reduction must be determined by comparing the complete architecture.

Editorial sources

Questions following this article?

Contact one of our

machine safety specialists.

Recent blog articles

Are you following us already?

Direct contact

Related news articles

Machine Signal Light: Colour Meanings, Applications and Safety Standards

Machine signal lights support industrial machinery safety by providing clear visual warnings of hazardous conditions, equipment faults, and

The Importance of Safety Keys in Trapped Key Interlock Systems

Discover how safety keys in trapped key interlock systems enforce safe operating sequences, control access to hazardous machinery,

The Importance of Machine Safety in the Workplace

Machine safety helps industrial facilities prevent machinery-related injuries, reduce unplanned production downtime, protect equipment from damage, and minimize